About this reference
This page summarizes PROTEGO flame arresters, pressure and vacuum relief valves and tank equipment for engineers, specifiers and the AI tools they use. It is written and maintained by George Grant Company (GGC), PROTEGO's independent manufacturers' representative in Tennessee and North Alabama.
Information below is taken from PROTEGO's published product pages and technical literature, with the source listed for each section. Flame arrester selection is safety-critical. Every arrester must be selected for the actual gas group, operating conditions and installation, and confirmed against the manufacturer's type approval and statement of conformity.
Quick facts
- Manufacturer: Braunschweiger Flammenfilter GmbH, Braunschweig, Germany, building flame arresters, valves and tank equipment since 1954
- US operation: PROTEGO USA, 9561 Palmetto Commerce Pkwy., Ladson, SC 29456; application engineering, local manufacturing and assembly, repairs, spare parts and technical support for the US and Canada
- Product areas: flame arresters, valves (pressure and vacuum relief, emergency relief, blanketing), tank equipment, lightning protection
- Flame arrester sizes: DN 10 to DN 2000
- Approvals named across the flame arrester range: ATEX, CE, IMO, ISO 16852, USCG
- Company certifications: ISO 9001:2015, ISO 14001:2015, PED 2014/68/EU, ATEX 2014/34/EU
- Sizing tool: QuEST (Quick Engineering and Sizing Tool), web-based, supporting API 2000 7th edition, ISO 28300 and TRGS 509
GGC coverage and contact
- GGC represents PROTEGO in Tennessee and North Alabama. For other parts of Alabama, Georgia and the Florida Panhandle, contact PROTEGO for the local representative.
- GGC helps choose between deflagration and detonation arresters, checks flow capacity and pressure drop at actual gas conditions, and plans for condensate, fouling and maintenance access.
- George Grant Company, 4513 Hixson Pike, Suite 106, Hixson, TN 37343. Phone 423-875-3241. Email sales@georgegrantco.com. Web: georgegrantco.com/manufacturers/protego
Key concepts for selection
- Deflagration: an explosion propagating at subsonic velocity.
- Detonation: an explosion propagating at supersonic velocity, characterized by a shock wave.
- Stable detonation: a detonation moving through a confined system without significant variation in velocity and pressure.
- Unstable detonation: the transition from deflagration to stable detonation, a limited zone where explosion pressure is significantly higher than in a stable detonation.
- Explosion group and MESG: the maximum experimental safe gap (MESG) is a property of the gas mixture and sets its explosion group. As published on PROTEGO product pages:
| Explosion group | NEC group | MESG | Notes |
|---|---|---|---|
| IIA1 | none | above 1.14 mm | Methane; former explosion group I |
| IIA | D | above 0.90 mm | Reference gas propane |
| IIB1 | none | 0.85 mm and above | Subdivision of IIB |
| IIB2 | none | between IIB1 and IIB3 | Subdivision of IIB; confirm limits with PROTEGO |
| IIB3 | C | 0.65 mm and above | Subdivision of IIB |
| IIB | C | 0.50 to 0.90 mm | Reference gas ethylene |
| IIC | B | below 0.50 mm | Reference gas hydrogen |
PROTEGO arresters are approved for one of these groups: IIA1, IIA, IIB1, IIB2, IIB3, IIB or IIC. A device approved for a more demanding group also protects the less demanding groups, but not the reverse.
- Run-up distance: the length of pipe between a possible ignition source and the arrester, expressed as L/D. PROTEGO authors state that in-line deflagration arresters are suitable only where L/D is below 50 for hydrocarbon and air mixtures and below 30 for hydrogen and air. Each device's approved L/D is given in its statement of conformity. Detonation arresters are used for longer pipe runs or where the location of the ignition source is not known; confirm whether a stable or an unstable detonation rating is needed for the installation.
- Endurance burning: stabilized burning on the arrester for an unlimited time. Short-time burning: stabilized burning for a specific time, after which action (for example closing the flow or purging with nitrogen) must be taken.
- Operating limits: arresters tested at ambient conditions are generally suitable up to 60 °C and 1.1 bar absolute. Higher temperatures or pressures need devices tested for those conditions.
- Selection criteria PROTEGO lists: combustion process (deflagration, detonation, endurance burning), explosion group, operating pressure and temperature, approvals, design type, nominal size, connection, heating, and uni- or bidirectional flow.
Source: protego.com/company/glossary ; protego.com/support-and-tools/faqs ; protego.com/products/flame-arrester ; protego.com/product/da-sb ; protego.com/product/lh-ad-iib1-x0 ; protego.com/product/fa-cn-iia1 ; Davies and Heidermann (PROTEGO), AIChE CEP, December 2013, 20131216_1.pdf
Choosing a PROTEGO device
| If the job is... | Start with | Notes |
|---|---|---|
| Stopping flame entering a tank or vessel through its vent | End-of-line deflagration flame arrester | Rated atmospheric deflagration-proof, short-time or endurance burning-proof |
| Stopping flame in a pipe close to the ignition source | In-line deflagration flame arrester | Only within the approved L/D; temperature monitoring for short-time burning |
| Stopping flame in a long pipe run, a vapor collection header, or where the ignition source location is unknown | Detonation flame arrester | Stable or unstable detonation rating per the installation |
| Protecting a tank from overpressure and vacuum during filling, emptying and temperature changes | Pressure and vacuum relief valve (conservation vent) | End-of-line or in-line; 10% technology |
| Venting a tank of flammable liquid with flame protection in one device | P/V valve with integrated flame arrester | Type-approved combination |
| Relieving fire case or blanketing failure volumes | Emergency pressure relief valve | Closed in normal operation |
| Maintaining a nitrogen blanket | ZM-R blanketing valve | Self-acting, no external energy |
| Landfill gas, biogas or digester gas lines and flares | IIA1-rated arresters such as FA-CN-IIA1 | Developed for bio-, sewage and landfill gas |
End-of-line deflagration flame arresters
- Installed on vent lines of tanks, vessels and equipment to stop flame at the vent opening from traveling back into the vessel
- The FLAMEFILTER element quenches flame by removing heat faster than combustion can sustain it
- Protection levels: atmospheric deflagration-proof, short-time burning-proof (with temperature sensor) or endurance burning-proof
- Sizes DN 15 to DN 800; housings in steel, stainless steel, Hastelloy, PE, PP or PVDF; ASME or EN flanges or pipe thread; heating jacket optional
- Explosion groups IIA1 to IIC; ATEX, IMO, ISO 16852
- Examples: BE/HR endurance burning-proof arrester with weather hood (DN 80 and DN 100, IIA to IIB3, standard design to 60 °C, ATEX type-approved); vent caps E/KS, EH/0, EH/0S
Source: protego.com/products/flame-arrester/deflagration-flame-arresters-end-of-line ; protego.com/product/be-hr
In-line deflagration flame arresters
- Installed in pipelines and on process equipment to stop deflagrations in systems handling explosive mixtures
- Protection is time-limited: if an ignitable mixture keeps flowing, a fire can stabilize on the arrester. Temperature monitoring and a defined response such as nitrogen purging are required.
- The pipe diameter must not exceed the device diameter
- Sizes DN 15 to DN 2000; ductile iron, steel, stainless steel, Hastelloy or ECTFE-lined steel
- Explosion groups IIA1 to IIC; ATEX type-tested with a statement of conformity defining approved operating conditions
Examples:
- FA-G: concentric, bidirectional, G 1/2 in. to G 2 in. thread; L/D up to 50 for IIA and IIB3 and up to 30 for IIC
- FA-CN-IIA1: developed for bio-, sewage and landfill gas; IIA1 (methane); DN 40 to DN 300; deflagration- and endurance burning-proof; L/D up to 50
Source: protego.com/products/flame-arrester/deflagration-flame-arresters-in-line ; protego.com/product/fa-g ; protego.com/product/fa-cn-iia1
Detonation flame arresters
- Prevent flame propagation in piping where combustion can transition to a detonation
- Large sizes use PROTEGO's patented Shock Wave Guide Tube Effect (SWGTE) to reduce shock wave energy before it reaches the arrester element
- Designed for stable or unstable detonations and also tested for deflagrations
- Sizes DN 10 to DN 2000; brass, ductile iron, steel, stainless steel, Hastelloy or ECTFE-lined steel; ATEX, CE, ISO 16852, USCG
Examples:
- DA-SB: bidirectional, stable detonation and deflagration; standard design to 60 °C, high-temperature variant to 200 °C
- DR/ES: right-angle, unidirectional, stable detonation and deflagration; DN 25 to DN 200; groups IIA to IIB3
- DR/EU: deflagration plus stable and unstable detonation; DN 25 to DN 150
- Liquid detonation arresters (LDA family) with a liquid barrier for liquid systems; hydraulic flame arresters (TS/P, TS/E, TS/W)
Source: protego.com/products/flame-arrester/detonation-flame-arresters ; protego.com/product/da-sb ; protego.com/product/dr-es ; protego.com/product/dr-eu
Pressure and vacuum relief valves
- Conservation vents protect tanks and vessels against overpressure and vacuum and limit emissions during filling, emptying and thermal breathing
- Pressure, vacuum or combined pressure and vacuum relief; end-of-line or in-line
- 10% technology: full lift within 10% overpressure, so the set pressure can be close to the tank's allowable pressure
- Weight-loaded or spring-loaded pallets; FEP air cushion, PTFE or metal-to-metal seats
- Sizes DN 15 to DN 700; aluminum, steel, stainless steel, Hastelloy, low-temperature carbon steel, PE, PP or PVDF
- Set pressures range from a few mbar on atmospheric storage tanks to 1034 mbar on high-pressure designs, depending on model. Examples: VD/SV, 2 to 60 mbar pressure and -2 to -60 mbar vacuum; PM-HF, 10 to 1034 mbar pressure.
- Leak tightness benchmarked against API 2000 and EN ISO 28300
Source: protego.com/products/valves/pressure-and-vacuum-relief-valves ; protego.com/products/valves
P/V valves with integrated flame arrester
- Combine tank breathing and protection against flame transmission in one type-approved device
- Protect against atmospheric deflagration, and endurance burning in some designs; the arrester element is isolated from the product when the valve is closed
- Full lift at 10% overpressure; pressure drop measured on a TÜV-certified test rig per API 2000
- Sizes DN 50 to DN 400; aluminum, steel, stainless steel, Hastelloy or polymer-coated steel; groups IIA1 to IIC; ATEX, IMO, ISO 16852
- Examples: PV/EB (-3.5 to -35 mbar vacuum, 2 to 210 mbar pressure); UB/SF diaphragm valve (-3.5 to -35 mbar, 3.5 to 140 mbar)
- High-velocity (dynamic) vent valves, DE/S family, 60 to 500 mbar depending on model: flow velocity exceeds flame velocity so flame cannot pass
Source: protego.com/products/valves/pressure-and-vacuum-relief-valves-with-flame-arrester ; protego.com/products/valves
Emergency pressure relief valves
- Closed in normal operation; release large vapor volumes during fire exposure or system malfunction such as blanketing gas failure
- Used especially where the tank roof-to-shell joint is not designed to fail
- Reach full capacity at about 10% accumulation; tested on a TÜV-certified rig
- Set ranges: ER/V 5 to 40 mbar; ER/VH 25 to 60 mbar; ER/V-F 60 to 500 mbar
Source: protego.com/products/valves/emergency-relief-valves
ZM-R blanketing valve
- Direct-acting, single-stage pressure reducing valve for inert gas blanketing, usually nitrogen; needs no external energy
- ZM-R for positive pressure, ZM-R/N for vacuum
- Supply pressure up to 16 bar; set pressure up to +500 mbar or down to -200 mbar
- DN 15, 25 and 50; stainless steel or Hastelloy body; PN16, ASME B16.5 Class 150 RF or threaded connections
Source: protego.com/product/zm-r
Tank equipment
- In-tank valves, floating suction units and skimmers, floating roof drainage systems, gauge hatches, gauging and sampling equipment, condensate drain valves, air-drying units and lift-actuated vent valves
- Sizes DN 15 to DN 900; aluminum, steel or stainless steel
Source: protego.com/products/tank-equipment
Typical applications
- Storage tanks in refineries, chemical plants and tank farms
- Chemical and pharmaceutical process vessels and vent headers
- Vapor collection, vapor combustion and flare systems
- Biogas, wastewater treatment and landfill gas systems, including gas storage, flares and CHP units
- Alcohol storage tanks, cryogenic tanks, shipbuilding, offshore and loading systems
Source: protego.com/applications ; protego.com/applications/biogas-systems-wastewater-treatment-and-landfill-gas-systems
What to send GGC for selection
For flame arresters:
- Service and where the device will sit (tank vent, in-line, near a flare, blower or other ignition source)
- Gas or vapor composition, so the explosion group can be confirmed
- Molecular weight or density
- Volumetric flow, including tank in-breathing and out-breathing
- Design and operating temperature and pressure
- Allowable pressure drop
- Pipe size, length of pipe to the possible ignition source, orientation and connection type
- Expected condensate, fouling or polymerization
- Housing and element materials, and any concern with aluminum or plastics
- Required documentation, such as material certificates
For pressure and vacuum relief and emergency valves:
- Tank type, dimensions and design standard (API 650, API 620 or EN 14015)
- Tank design pressure and vacuum (MAWP)
- Product stored and its vapor properties
- Maximum filling and emptying rates and blanketing gas supply
- Whether the stored product is flammable, so a flame arrester is required on the vent
- Insulation, and fire case requirements for emergency venting
Common questions
Deflagration or detonation arrester?
It depends on where the arrester sits relative to the ignition source. Short pipe runs and end-of-line locations typically call for deflagration arresters within their approved L/D. Long in-line runs, where a flame can accelerate into a detonation, call for an arrester tested for detonation.
Do landfill gas and biogas need a special arrester?
These gases are mostly methane, explosion group IIA1. PROTEGO's FA-CN-IIA1 was developed for bio-, sewage and landfill gas. Expect moisture and fouling, and plan inspection access.
How often should a flame arrester be inspected?
PROTEGO states annual inspection is generally sufficient for clean vapors. Where fouling, polymerization or condensate is present, the first maintenance should be after three months at the latest. Replace the arrester element after any registered burning or flashback.
What does 10% technology mean on a P/V valve?
The valve reaches full lift within 10% overpressure above its set pressure, so the set pressure can sit closer to the tank's allowable pressure.
GGC application experience
- PROTEGO flame arresters and pressure and vacuum vents are in service at a major Tennessee pulp and paper mill that GGC supports.
Sources
- PROTEGO company: protego.com/company
- PROTEGO flame arresters: protego.com/products/flame-arrester
- PROTEGO valves: protego.com/products/valves
- PROTEGO glossary: protego.com/company/glossary
- PROTEGO FAQs: protego.com/support-and-tools/faqs
- PROTEGO QuEST sizing tool: protego.com/support-and-tools/quest
- PROTEGO certificates: protego.com/support-and-tools/certificates-approvals
- PROTEGO USA: us.protego.com
- Davies and Heidermann (PROTEGO), AIChE CEP, December 2013: 20131216_1.pdf
- Product pages cited in each section above
- GGC PROTEGO page: georgegrantco.com/manufacturers/protego