Application Notes

RNG Gas Quality Monitoring: What to Measure Before Pipeline Injection

A pipeline does not accept renewable natural gas on a promise. It accepts it on proof, measured continuously at the point of injection against the limits in its tariff. Miss a limit and the receiving pipeline or utility can shut the interconnect in, which stops revenue on a plant that only earns money when gas flows.

Our video RNG Gas Quality 101: What’s Actually in Landfill Gas explains what raw landfill gas contains. This note is the practical companion: which parameters the tariff limits, where to measure them along the upgrading train, which belong on continuous analyzers and which go to the lab, and the selection details that decide whether your data holds up.

What the tariff limits

Every pipeline and utility writes its own limits, so your interconnect agreement is the only number that counts. The ranges below show what RNG producers commonly face across published U.S. tariffs and the American Biogas Council’s pipeline recommendation.

ParameterCommon tariff limitWhy the pipeline caresUsually measured
Oxygen (O2)0.2% to 0.4% is common; some systems allow as little as 10 to 50 ppmCorrosion, and reactions with other constituents in the lineContinuous
Hydrogen sulfide (H2S)0.25 grain per 100 scf (about 4 ppm)Toxic and corrosive, especially with water presentContinuous
Water vapor7 lb per MMscfForms acids with H2S and CO2; condenses or freezes in the lineContinuous
Carbon dioxide (CO2)2% to 3%Corrosion with water; lowers heating valueContinuous
Heating valueMinimum about 950 to 980 Btu/scf, maximum about 1,100Customers’ burners are set for a narrow rangeContinuous
Nitrogen and total inertsNitrogen 3% to 4%, total inerts 4% to 5%Dilute heating value; nitrogen tracks air leaking into the wellfieldContinuous or periodic
Total sulfur0.75 to 20 grains per 100 scf, varies widelyCorrosion and odorant interferencePeriodic lab
Siloxanes, VOCs, halocarbons, bacteriaTrace limits set by each tariffEquipment damage and health-protective limitsPeriodic lab

Sources: American Biogas Council RNG purity recommendation, CenterPoint Energy RNG quality standards, Southern Star RNG specification update, Atmos Energy gas quality specifications, Minnesota Energy Resources RNG testing procedures.

Where to measure

Measure at each step that can fail, not only at the injection point. By the time the utility’s own analyzer sees a problem, the plant is already shut in. Points upstream give operators time to correct before the gas reaches the interconnect.

  1. Plant inlet (raw gas). Methane, CO2, O2 and H2S tell operators what the wellfield is delivering. Rising O2 and nitrogen point to air leaking into the collection system, and that is fixed in the wellfield, not the plant.
  2. After H2S removal. H2S here shows whether the treatment media is still working. Watching the trend lets the plant schedule a media change before breakthrough rather than after.
  3. After drying. Water dew point confirms the dryer is doing its job before wet gas reaches the CO2 removal step.
  4. After CO2 and nitrogen removal. Methane, CO2 and O2 show whether membranes or PSA are holding the product on spec. Oxygen that survives this step goes straight to the pipeline.
  5. Product gas before the injection valve. O2, H2S, water, CO2 and heating value on the finished gas, ahead of the utility’s measurement, so off-spec gas can be diverted before it is ever offered to the pipeline.
  6. Tail gas and flare. Flow and methane in the reject stream close the plant’s mass balance and show methane slip. See Measuring Landfill Gas Flow to Flares.

Continuous analyzers vs. periodic lab testing

The parameters that can change in minutes belong on continuous analyzers. The ones that change slowly, or that no practical field analyzer measures, go to a certified lab on a schedule the tariff sets.

  • Continuous: O2, H2S, water, CO2 and heating value or methane. Many utilities require these on line and in real time at the interconnect, and producers need the same readings upstream to stay ahead of them.
  • Periodic lab: siloxanes, total sulfur, VOCs, halocarbons and other trace constituents, typically at startup and then quarterly or annually. Landfill gas usually carries the longest list, because of what is buried in the cell.

A lab result tells you the gas was in spec on the day of the sample. Only a continuous measurement tells you it stayed there.

Selection details that decide whether the data holds up

  • Range at the limit, not at full scale. An analyzer reading 0 to 25% O2 cannot resolve a 10 ppm limit. Choose ranges so the tariff limit sits well inside the measurable span, and check whether the plant needs a ppm range at the product and a percent range at the inlet.
  • Cross-sensitivity to H2S. Some oxygen sensors are poisoned or biased by H2S, which landfill gas always carries. Ask how the O2 measurement tolerates H2S at the inlet concentration, and what that does to sensor life.
  • Moisture in the units the tariff uses. Tariffs state water in lb per MMscf; many analyzers read dew point. Make sure the conversion uses the line pressure at the measurement point, or the reading and the limit will not agree.
  • The sample system. Most bad gas quality data starts in the sample line, not the analyzer. Specify filtration and liquid knockout, heat tracing where condensation is possible, materials that do not absorb H2S, and a sample path short enough that lag time stays in seconds, not minutes.
  • Hazardous area rating. Analyzer shelters and skids at RNG plants are commonly classified areas. Confirm the analyzer’s approvals or plan for purge and pressurization or an intrinsically safe design.
  • Calibration and validation. Plan the calibration gases, interval and record-keeping up front. Utilities may ask for proof that the producer’s analyzers were in calibration when a reading was disputed.
  • Outputs and interlocks. 4-20 mA or Modbus to the plant control system, a fault alarm that behaves like an off-spec alarm, and a clear tie to the divert valve.

When gas goes off spec

When product gas leaves the tariff limits, the utility can shut the interconnect in immediately, and getting back in takes proof. One Midwest utility, for example, requires at least one continuous hour of in-spec readings on its real-time monitoring before injection restarts (Minnesota Energy Resources).

While the plant is shut in, the gas still has to go somewhere, usually the flare. That makes the flare flow measurement part of the same compliance picture: it documents how much gas was destroyed rather than sold. The upstream analyzers in the section above are what keep those hours short.

Specification checklist

Send us these and we can recommend analyzers, ranges and sample systems for each point:

  • The interconnect’s gas quality limits (the tariff or interconnect agreement section)
  • Raw gas composition: CH4, CO2, N2, O2 and H2S, with the range you expect
  • Upgrading process: H2S removal method, dryer type, membranes or PSA
  • Pressure and temperature at each measurement point
  • Which points need continuous measurement and which are covered by lab testing
  • Area classification at the analyzer location
  • Required outputs (4-20 mA, Modbus) and the divert or shut-in logic
  • Calibration and documentation expectations from the receiving utility

How George Grant Company helps

George Grant Co. represents AMI (Advanced Micro Instruments) process analyzers for oxygen, H2S and moisture across Tennessee, Georgia, Alabama and the Florida Panhandle. We help RNG developers, EPCs and operators choose the analyzer, range and sample system for each point in the upgrading train, and we support start-up and calibration locally. The same plants also use lines we carry for landfill gas flow, gas detection, flame arresters and purge and pressurization, so one call covers most of the instrumentation around the skid.

Related resources

This application note is general guidance. The receiving pipeline’s tariff and your interconnect agreement set the actual limits, test methods and frequencies.

George Grant Co. | Hixson (Chattanooga), TN | 423-875-3241 | sales@georgegrantco.com | www.georgegrantco.com