Application Notes

Gas Detection for Anaerobic Digesters and Biogas Systems

Anaerobic digesters turn sludge into biogas that is typically 55 to 70 percent methane, with hydrogen sulfide and moisture along for the ride. That gas is an asset when it fuels boilers, generators or an RNG system. Anywhere it leaks, it is a fire, toxic and oxygen deficiency hazard at the same time. As more Tennessee utilities add digesters, biogas-to-power and RNG projects, gas detection deserves the same design attention as the process equipment around it.

Three hazards, three sensors

Methane (combustible). Methane becomes flammable at 5 percent by volume in air, its lower explosive limit (LEL). Detectors report in percent of LEL, so 100% LEL means 5 percent methane. Methane is lighter than air and collects at ceilings and high points.

Hydrogen sulfide (toxic). H2S is heavier than air and settles in pits, galleries and low areas. At high concentrations it deadens the sense of smell, so the rotten-egg odor is not a warning anyone should rely on. NIOSH lists 50 ppm as immediately dangerous to life and health.

Oxygen deficiency. Biogas and other gases can displace oxygen in enclosed spaces. OSHA treats any atmosphere below 19.5 percent oxygen as oxygen deficient.

Choosing the right sensor technology

Hazard Recommended technology Why
Methane Infrared Infrared sensors are not poisoned by H2S or siloxanes, both common in biogas, and keep reading accurately in low-oxygen air. Catalytic bead sensors can lose sensitivity in exactly these conditions.
H2S Electrochemical Accurate at low ppm levels for personnel protection
Oxygen Electrochemical Detects both deficiency and enrichment

Where a sensor would be hard to reach for calibration, specify a remote sensor with the transmitter at working height, or a sample-draw system.

Where to detect in a digester complex

A common gap is not a missing detector but a detector in the wrong place: a methane sensor mounted low, or an H2S sensor near the ceiling.

Area Gases to monitor Mounting
Digester gas handling and compressor rooms Methane, H2S Methane within 12 in of ceiling; H2S 12 to 18 in above floor
Sludge heating and boiler rooms Methane, CO where gas is burned Methane high, near gas train and burner
Sludge pump and piping galleries H2S, oxygen, methane H2S low, oxygen at breathing zone, methane high
Pits, tunnels and wet wells H2S, oxygen, methane As above; consider sample-draw for deep spaces
Waste gas burner and flame trap areas Methane High points near valves and flame arresters
Biogas-to-power or RNG skids Methane, H2S At skid enclosure high points and near connections

Alarm strategy

  • Two alarm levels per gas. A warning level that starts or increases ventilation and alerts the control system, and a danger level that adds horns and strobes.
  • Indication at every entrance. Staff should know the room’s status before they open the door. A strobe or display outside the room does that.
  • Fault alarms to SCADA. A failed or missing sensor should alarm just like gas does.
  • Area classification drives the hardware. NFPA 820 and the National Electrical Code determine which areas are classified, and detectors there must carry approvals for that classification.

What to put in the specification

  1. Gases, ranges and sensor technology for each area, in a detector schedule.
  2. Mounting heights by gas, shown on the plans.
  3. Warning and danger setpoints and the action tied to each.
  4. Outputs to the plant control system (4-20 mA or Modbus) and fault reporting.
  5. Approvals for the area classification.
  6. Factory-trained start-up, calibration, and operator training, plus spare sensors and calibration gas.

Calibration is the part that gets skipped

Electrochemical sensors wear out, typically in two to three years, and every detector drifts. A detector nobody calibrates is worse than none, because people trust it. Build a calibration interval and a sensor replacement plan into the project, not just the equipment.

How George Grant Company helps

George Grant Company is the exclusive Tennessee municipal representative for a U.S.-made line of fixed gas detection equipment. We help engineers with detector selection and specification language, and we handle start-up, calibration and operator training locally. For existing plants, we offer a no-cost walk-down of your digester complex to compare where you detect today with where the gas risk is.

Request our gas detection specification template (form below)

This application note is general guidance. The engineer of record is responsible for area classification, final specification and alarm setpoints.